Loading...
Ordinance No. 14,475ORDINANCE NO. 14,475 AN ORDINANCE OF THE CITY COUNCIL OF THE CITY OF BAYTOWN, TEXAS, APPROVING CHANGE ORDER NO. 11 TO THE BAYTOWN AREA WATER AUTHORITY 6 MGD SURFACE WATER TREATMENT PLANT PROJECT BETWEEN THE BAYTOWN AREA WATER AUTHORITY AND PEPPER LAWSON WATERWORKS, LLC; AND PROVIDING FOR THE EFFECTIVE DATE THEREOF. **************************************************************************************************** WHEREAS, the Baytown Area Water Authority's enabling legislation requires that the City Council approve certain agreements before Baytown Area Water Authority ("BAWA") enters into the same; and WHEREAS, on August 19, 2020, the Board of Directors of BAWA approved Change Order No. 11 to the Baytown Area Water Authority 6 MGD Surface Water Treatment Plant Project between the Baytown Area Water Authority and Pepper Lawson Waterworks, LLC; and WHEREAS, the City of Baytown desires to approve such change order; NOW THEREFORE, BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF BAYTOWN, TEXAS: Section 1: That the recitals set forth hereinabove are hereby found to be true and correct and are hereby adopted. Section 2: That the City Council of the City of Baytown, Texas, hereby approves Change Order No. 11 for the Baytown Area Water Authority 6 MGD Surface Water Treatment Plant Project between the Baytown Area Water Authority and Pepper Lawson Waterworks, LLC, which change order is attached hereto as Exhibit "A" and incorporated herein for all intents and purposes. Section 3: This ordinance shall take effect immediately from and after its passage by the City Council of the City of Baytown. INTRODUCED, READ and PASSED by the affirmative vote of the City Council of the City of Baytown this the 315' day of August, 2020. ON CAPETILLO, Ma or ATT ST: LETICIA BRYSCH, City lerk APPROVED AS TO FORM: KAREN L. HORNER, Interim City Attorney RAKaren Homer\DocumentsTiles•City Council Ordinances\2020\August 31\ApprovingBAWAChangeOrderNoI Ldoc BAYTOWN AREA WATER AUTHORITY Change Order No. 11 6.0 MGD SURFACE WATER TREATMENT PLANT PO: 1806021 Date: 13-Aug-20 CO 11.1 is to request for extra cost due to City of Houston's additional flow meter signal modificaiton. CO 11.2 is for the additional cost for drain line modifications in response to RFP #013. CO 11.3 is for the shunt trip disconnect for elevator in order to meet code for inspection. CO 11.4 is for the protective separation basins required for the sodium chlorite and hydrochloric acid stored in the chemical containment area. This will ensure the safety of the occupants from chlorine gas. Add or Delete Items: e n Description Unit a i Unit Price Total 11.1 City of Houston Flow Meter Signal Modifications (PCO 073) 1 LS 9,026.80 $ 9,026.80 11.2 Drain Line Modifications (PCO 07413) 1 LS 169,163.74 $ 169,163.74 11.3 Shunt Trip Disconnect for Elevator (PCO 075) 1 LS 4,120.38 $ 4,120.39 11.4 Chemical Vat Separators (PCO 077) 1 LS 5,905.44 $ 5,905.44 Total Contract Summary: $ 188,216.36 Original Revised 1 10riginal Contract Price $52,186,000.00 2 Owner Contingency $0.00 Previous Change Orders This Change Order Remaining Contingency 3 Change Orders Previous Change Orders $ (3,292,800.76) This change order $ 188,216.36 4 Revised Contract Price $52,186,000.00 $49,081,415.60 Original Contract Duration 1095 Previous Extensions 0 This Change Order 0 Revised Duration - Calendar Days 1095 6L<rt r) G C 08/13/2020 Contractor: PLW Wa erworks, LLC Date Director of Public Works & Engineering Date Chris Smith, Executive Vice President Frank O. Simoneaux Jr. P.E. / 8-/3-Zo 20 _ Consultant s I Carter, Inc. Date City Manager Date Richard L. Davis, ICMA-CM PLw waterworks June 24, 2020 Mrs. Andrea Brinkley Assistant Director Baytown Area Water Authority The City of Baytown 2401 Market St. Baytown, TX 77520 Re: CPR No. 73 BAWA 6 MGD Surface Water Treatment Plant BAWA Job No. 1806021 Mrs. Brinkley, Please see attached proposal for the City of Houston Flow Meter Signal Modifications per RFP #012. This change will result in a increase in the amount of $9,026.80 Please feel free to contact me at (713) 301-8637 with any questions or concerns. Regards, PLW Waterworks ) � Katy Drown Project Manager Page 1 Baytown Area Water Authority BAWA 6 MGD Surface Water Treatment Plant BAWA Job No. 1806021 City of Houston Flow Meter Signal Modifications Scope of" ork City of Houston Flow Meter Signal Modifications CPR No.: #073 Date: 06/24/20 PLW Job No.: P3T Non -Taxed Labor Material Subcontract Taxed Mat'VE ui Unit Total Unit Total Unit Total Unit Total Item No. Description Unit Cost Cost Cost Cost Cost Cost Cost Cost 1 City of Houston Flow Meter Modifications i I Pfieffer and Sons & Prime Controls 1 LS S - S $ S $ 7,62077 S 7.62077 5 - s Direct Cost Subtotal 7,62077 Small Tools 1 5 00o n/a - n/a n/a Equipment Burden 50 00o n/a n/a n/a n/a Tax r 8 25oo n/a n/a n/a Subtotal 2 7,62077 Overhead & Profit t 15 Oo o 1,143 12 Subtotal 3 8,763 89 Bonds & Insurance (eb 3 Ooo 26292 Subtotal 4 9,02680 Total of all columns 9 026 80 Other Grand Total Cost 9,026.80 Page 2 10 JONES CARTER RFP NO.: 012 REQUEST FOR PROPOSAL (RFP) 1. PROJECT NAME: 6 MGD Surface Water Treatment Plant 2. J&C PROJECT NO.: 09986-0002-00 3. CONTRACTOR: Pepper Lawson Waterworks 4. SUBMITTED TO: Katy Drown S. SUBJECT: City of Houston Flow Signal 6. REFERENCE: 7. REF. DWG. NO.: 2-E-1 8. REF. SPEC. NO.: N/A 9. DESCRIPTION OF WORK: The Contractor is requested to furnish a price proposal for the below described work. Please complete, sign, date, and return a proposal at your earliest convenience. Please attach a detailed cost breakdown to your proposal. BAWA has requested that the flow signal from the City of Houston flow meter be added and implemented to the Plant Overall SCADA system. Please provide a cost for the following items: 1. NEMA 4X enclosure that includes all ancillary items to connect to City of Houston flow meter signal. 2. Conduit from new enclosure to stubbed -up conduit 2-001-1007. 3. Signal wiring from new enclosure to 24-PLC-001 through conduit 2-001-1007. 11. Requestor's Name & Signature: Larry Weppler Date: 6/9/20 The Contractor acknowledges that this RFP is to be used to request pricing information only, and does NOT constitute a contract modification. The Contractor is NOT AUTHORIZED/DIRECTED to perform this work UNTIL/PRIOR TO written notification that a contract modification is approved. 6;wp\docs\const\forms\rfi or rfp\rfpform.doc REV 9.• I3 0; PFEIFFER & SON, LTD. Electrical Contractors PHONE - (281) 471-4222 * FAX - (281) 471-6856 116 N. 16TH ST. * P.O. BOX 1116 LA PORTE, TEXAS 77572 jonathan@pfeifferandson.com pfeifferandson.com CHANGE ORDER BID DATE: JUNE 23, 2020 TO: PLW WATERWORKS ATTN: MRS. KATY DROWN PROJECT: BAWA 6 MGD SURFACE WATER TREATMENT PLANT We request, as discussed, the below listed change order for the BAWA 6 MGD SWTP project. Please see the price below for your consideration and reference the below list of exclusions and clarifications as well as the attached documents. We propose to furnish all material, labor, equipment, and supervision in a safe and skillful manner for a complete and functioning system. RFP 12 ELECTRICAL — 2-FE/FIT-001 SIGNAL SPLITTER ENCLOSURE $7,620.77 To avoid confusion, we offer the following clarifications: 1. Above price includes provision and installation of NEMA 4X signal splitter enclosure and all conduit and conductors for connection of that equipment for transmission of the flow signal from the splitter enclosure to 24-PLC-001 2. Pricing includes required programming modifications to make flow signal from 2-FE/FIT-00I visible in plant SCADA system. 3. See attached subcontractor quote and pricing breakdown for additional detail. 4. Bond is included. 5. We will provide insurance coverage in accordance with the specifications. Builder's Risk insurance covering our scope of work is not included, as this should be the General Contractor's responsibility, and therefore we assume no responsibility for theft or vandalism of installed material. Additional coverage specifically required by the contractor may necessitate additional premium charges. We appreciate this opportunity to quote on this project. If you have any questions or need additional clarifications, please call me at (281) 471-4222. Sincerely, PFEIFFER & SON, LTD. Jonathan Pfeiffer REGI ILATED BY THE TEXAS DEPARTMENT OF LICENSING AND REGULATION CONTRACTOR LICENSE# 18259 PO BOX 12157 ' AUSTIN. TX 78711 (800) 803-9209 • (512) 463-6599 • ,.,•„ [— sMte M ud—plainU ADOPTED ADMINISTRATIVE. RIVES 73 51 (<1 F.LF.CTRICAI CONTRACTORS RESPONSIBILITIES 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 PFEIFFER&SON, LTD. Electrical & Telecommunication Contractors PFEIFFER AND SON JOB # 4200119 CHANGE ORDER REQUEST Date: 6/23/2020 Project: BAWA 6MGD SWTP Description: Installation of signal splitter enclosure and modifications to plant SCADA for monitoring of 2-FE/FIT-001 General Labor Supervisory Labor Subtotal items 1 and 2 Labor Burden 55% x Item 3 Cost of Materials Equipment Cost of Transportation Subcontractor Subtotal items 3,4,5,E and 7 Cost of Insurance 4% x item 8 Cost of Bonds (7.4.2.2.4) Subtotal lines 8,9 and 10 Overhead 10% Profit 5% Not Used Total change order amount items, items 11,12,13 and 14 Page 1 30.00 hours x $ 3.00 hours x $ 29.9 897.00 55.0 165.00 1,062.00 584.10 1,460.54 195.00 0.00 2,895.00 6,196.64 247.87 182.24 6,626.75 662.68 331.34 n nn $ 7,620.77 :DR=ME -comom 12144 DAIRY ASHFORD, BLDG 3 • SUGAR LAND, TX 77478 PHONE 713-244-9747 0 FAx 713-244-9717 June 18, 2020 To: Pfeiffer & Sons 116N16thSt La Porte, TX 77571 Attn: Jonathan Pfeiffer Mark Antley Ref: BAWA 6 MGD Surface Water Treatment Plant Project Work Authorization No. 265 Prime Controls Change Order No.: PCO-008 PRIME CONTROLS PROPOSAL Prime Controls is pleased to offer this proposed change order (PCO) to add the City of Houston Flowmeter Signal into the SCADA System as per RFP-12 with the referenced Baytown Area Water Authority 6 MGD Surface Water Treatment Plant project as described hereafter. Our Scope of Work shall include applicable products and services specified to be provided in the following bid specifications: The offering is complete with the exception of those items specifically excluded within the "Exclusions" section of this proposal. Equipment and Materials to be provided by Prime Controls include the following major items: ITEM EQUIPMENT 1. One (1) NEMA 4X Wall Mount Enclosure and Backpanel (Panel size to match City of Houston Enclosure) 2. One (1) 24VDC Surge Suppressor 3. Lot terminal blocks, wire tags, tie wraps, etc. Services to be provided by Prime Controls include the following major items: ITEM SERVICES 1. VTSCADA HMI Programming Mods to add the City of Houston Flowmeter Signal to HMI 2 AB PanelView HMI Programming Mods to add the City of Houston Flowmeter Signal to Local HMI on PLC Panel 3. PLC Programming Mods to add the City of Houston Flowmeter Signal to Local HMI on PLC Panel 4. Field terminations within City of Houston Flowmeter and new enclosure for pulse output signal S. Field terminations with PLC Panel to add new signal Page 1 of 2 PRIME ONMOLS PROPOSAL CLARIFICATIONS ITEM CLARIFICATION 1. Prior to commencement of work, Prime Controls requests an executed copy of this change order request. We expect this change will be accepted in a timely manner. Prime Controls is not liable for schedule delays associated with this change in the scope of work. 2. Pricing shall be valid for 30 days only from proposal date. 3. Acceptance of an order shall be subject to the attached General Terms & Conditions. These General Terms and Conditions are superseded by current Master Service Agreements (MSAs), Contracts, Subcontracts and/or Blanket Purchase Orders that authorize this work. EXCLUSION ITEM EXCLUSION 1. Conduit and wiring additions 2. Physical installation of control panel (to be provided by Pfeiffer) PROPOSED CHANGE ORDER PRICING ITEM DESCRIPTION PRICING 1 City of Houston Flowmeter Signal Addition $2,895.00 Proposal Approval Approved by (print): Signature: Date: We sincerely appreciate this opportunity and look forward to being of service for this work. Thanks again and please feel free to call if there are any questions. Sincerely, Prime Controls, LP Michael Nivong Project Manager 713-244-9747 m.nivong@prime-controls.com Prime Controls Proposal Page 2 of 2 ptvv- waterworks August 7, 2020 Mr. Andrea Brinkley Assistant Director Baytown Area Water Authority The City of Baytown 2401 Market St. Baytown, TX 77520 Re: CPR No. 74 BAWA 6 MGD Surface Water Treatment Plant BAWA Job No. 1806021 Mrs. Brinkley, Please see attached proposal for the storm drain line modifications and re-route of chemical containment/storm lines, per RFP #013. Total Construction duration will be approximately 4 weeks. This change will result in a increase in the amount of $169,163.74. Please feel free to contact me at (713) 301-8637 with any questions or concerns. Regards, PLW Waterworks Katy Drown Project Manager Page 1 Baytown Area Water Authority BAWA 6 MGD Surface Water Treatment Plant BAWA Job No. 1806021 Sanitary Drain Line Modifications Scope of Work Chemical Area Drainage Modifications CPR No.: #074 Date: 08 07 20 PLW Job No.: P3T Non -Taxed Labor Material Subcontract Taxed Mat'I/E ui Unit Total Unit Total Unit Total Unit Total Item No. Description Qty Unit Cost Cost Cost Cost Cost Cost Cost Cost 1 Project Staff (4 Weeks Total Construction Activities) Senior Project Manager 50 HRS $ 145.00 $ 7,250.00 $ $ $ $ $ $ Superintendent 80 HRS $ 121.00 $ 9,680.00 $ $ $ $ $ $ Project Engineer 20 HRS $ 85.00 $ 1,700.00 $ $ $ $ $ $ 2 Loading Dock Type "A" Inlet Modifications (2 Weeks Straight Time) 2.1 Foreman 40 HRS $ 65.00 $ 2,600.00 $ $ $ $ $ $ 22 Sawcut approx 150' x 6' section of pavement and haul off I LS $ - $ - $ $ $ $ $ 9,734.00 $ 9,734.00 2.3 Operator and Mini Excavator (removal of c-sand) 60 HRS $ 50.00 $ 3,000.00 $ $ $ $ $ 37.50 $ 2,250.00 2.4 (2) Laborers shoveling and breaking up c-sand 110 HRS $ 39.00 $ 4,180.00 $ $ $ $ $ - $ - 2.5 Core 8" hole in existing manhole I LS s . $ - $ - $ - $ - $ ncluded above $ - 2.6 Place low strength grout (PLW purchase order pricing) 6 YDS $ 38.00 $ 140.00 $ - $ - $ - $ - $ - $ - 2.7 Install 8" PVC (2 Pipe Fitters, 5 Days) 80 HRS $ 45.00 $ 3,600.00 $ 4,294.73 $ 4,294.73 $ $ $ $ Pipe comes in 20' sections, cut, fit and install acc on pipe 2,8 Supply and Install Bank Sand 34 CYDS $ 38.00 $ 304.00 $ 12.50 $ 425.00 $ $ $ $ 2.9 Supply and Install c-sand and compact 243 TONS $ 38.00 $ 1,520.00 $ 27.50 $ 6,682.50 $ $ $ 225.00 $ 1,125.00 2.10 Lull and Operator; Unload and assist in placng pipe 50 HRS $ 50.00 $ 2,400.00 $ - $ - $ $ $ 81.25 $ 3,250.00 2.11 Form Pad (2 Carpenters, 4 Hours) 8 HRS $ 45.00 $ 360.00 $ 109.00 $ 2,289.00 $ $ $ . $ 2.12 Form, Place and Finish Concrete 972 SQFT $ - $ - $ - $ - $ 10.00 $ 9,720.00 $ 250.00 $ 250.00 2.13 Road Plates (Including Delivery / Pickup) I MO $ - $ - $ - $ - $ - $ - $ 1,200.00 $ 1,200.00 3 Chemical Containment Drainage Line Modifications (2 Weeks Straight Time) 3.1 Foreman 110 HRS $ 65.00 $ 7,150.00 $ $ $ $ $ $ - 3 2 Sawcut approx 135' x 6' section of paving I LS $ - $ - $ $ $ $ ncluded above $ 3.3 Operator and Mini Excavator (removal of c-sand) 40 HRS $ 55.00 $ 2,200.00 $ $ $ $ $ 3'.5� $ 1,500.00 3.4 Operator and Mini Excavator (premium time) 20 HRS S 82.50 $ 1,650.00 $ $ $ $ $ 3'.5'; $ 750.00 3.5 (2) Laborers shoveling and breaking up c-sand 100 HRS $ 35.00 $ 3,500.00 $ $ $ $ $ - $ - 3.6 Excavator and Operator 60 HRS $ 65.00 $ 3,900.00 $ $ $ s $ 14808 $ 8,884.80 3.7 Delivery/Pickup 2 EA $ . $ $ $ $ $ $ 5!"1.00 $ 1,000.00 3.8 Supply and Install Bank Sand 90 CYDS $ 38.00 $ 1,520.00 $ 12.50 $ 1,125.00 $ - $ - $ 225.0'j $ 1,350.00 3.9 Install 8" PVC (2 Pipe Fitters, 5 Days) 400 LF $ I5.00 $ 6,000.00 Included Above $ $ $ $ $ Pipe comes in 20'sections, cut, fit and install acc on pipe 3.10 Install c-sand and compact 210 TONS $ 35.00 $ 1,400.00 $ 27.50 $ 5,775.00 $ $ $ 225.00 $ 1,350.00 3.11 Form, Place and Finish Concrete 834 SQFT $ - $ - s $ $ N.D.. $ 8,340.00 $ 250.00 $ 250.00 3.12 Street Sweeper 2 WKS $ - $ . $ $ $ - $ - $ 600.00 $ 1,200.00 Direct Cost Subtotal 64,054.00 20,591 23 18,060.00 34,093.80 Small Tools r(y 5.0% 3,202.70 n/a - n/a n/a Equipment Burden @ 50.0 % n/a n/a n/a n/a Tax (ie 8.25% n/a n/a n/a 2,812.74 Subtotal 67,256.70 20,59123 18,060.00 36,906.54 Overhead & Profit (ru 15.0% 10,088.51 3,088.68 2,709.00 5,535.98 Subtotal 3 77,345 21 23,679.91 20,769.00 42,442.52 Bonds & Insurance a! 3.00o 2,320.36 710.40 623.07 1,273 28 Subtotal 79,665.56 24,390.31 21,392.07 43,715.79 Total of all columns 169,163.74 Other Grand Total Cost 169,163.74 Page 2 J O N E S CARTER RFP NO.: 013 Amendment REQUEST FOR PROPOSAL (RFP) 1. PROJECT NAME: 6 MGD Surface Water Treatment Plant 2. J&C PROJECT NO.: 09986-0002-00 3. CONTRACTOR: Pepper Lawson Waterworks 4. SUBMITTED TO: Katy Drown 5. SUBJECT: Chemical Area Drainage Modifications 6. REFERENCE: Attached Markups 7. REF. DWG. NO.: N/A 8. REF. SPEC. NO.: 9. DESCRIPTION OF WORK: The Contractor is requested to furnish a price proposal for the below described work. Please complete, sign, date, and return a proposal at your earliest convenience. Please attach a detailed cost breakdown to your proposal. t$ -W'afku PS attached FHaF1(UP5— d. lmstal•I-a 4' wr3' X 4" eefgreEepdrt disehaFgeef pipe ashemwtt 2. Loading Dock Type "A" Inlet Modifications a. Grout fill the manhole to an elevation of 26.46 with lightweight or low strength grout b. Core through manhole and install 155.5 LF of 8" PVC stormwater pipe at a 0.33% slope as shown in the attached markups c. Route the pipe as shown in the attached markups d. Install a 4' x 3' x 4" concrete pad at discharge of pipe as shown e. Remove and replace concrete pavement per detail sheet 0-C-12 Amendment: 3. Chemical Containment Drainage Line Modifications a. Cut and plug the 12" DI -SS line at an elevation of 24.5 as shown in the attached markups b. Install a 45° Bend at location of cut and route 375.5 LF of 8" PVC chemical pipe at a 0.33% slope as shown in the attached markups c. Core through Manhole No. 2 located next to the Backwash Equalization Basin d. Remove and replace concrete as needed for installation of the 8" PVC line per detail sheet 0-C-1 11. Requestor's Name & Signature: Larry Weppler Date: 6/9/20 The Contractor acknowledges that this RFP is to be used to request pricing information only, and does NOT constitute a contract modification. The Contractor is NOT AUTHORIZED/DIRECTED to perform this work UNTIL/PRIOR TO written notification that a contract modification is approved. I:wp\dots\const\forms\rfl or rfp\rfpform.doc REV 9 14/00 rwrzs: xo. .,vrrsxx a,r,e--_-- ------ — — — — — MATCH LINE SHEET 1-C-22 — -o-a — ---- --------_---- ^--- l A �� 1— 1 rr r -,.. Fe. 4 " I;`I.:....•e.�. .«.¢,I l , l� -- ---............_ - I - �-- '+ -- ------------- -- � �- II ...� I eeT [a..wuna' �� .ne M,,uznnon Ili 1- � --- r m� YARD PIPING SHEET 6 OF 16 I I e�°b'� n. -•M• � i•�`"' s• nw� I __—____—' „e � ______ I II. _ I ���� JI JONfi6 CA`ATfi'R K �a MATCH L/NE SHEET 1-C-28 - Oyu, a 4 v Aggregate Technologies, Inc. 10700 Tower Oaks Blvd. Houston, TX 77070 (281) 579-7229 Toll Free: 877-SLABSAW red For PEPPER-LAWSON WATERWORKS 1725 HUGHES LANDING BLVD SUITE 1200 The Woodlands, TX 77380 Quote Quote: 02473 Quote Date: 7 Aug 2020 Quote Expires: 9 Sep 2020 Job Name: CEDAR PORT AGGREGATES TERMINAL Task Type(s): DSS,CD Sales Rep: CHRISTOPHER ALLEN (832)621-6291 Job Site Address 5341 E Grand Pkwy S Baytown, TX 77523 Oty Description Price Total 1 SAWING -SLAB Length: 9,484.00 EACH 9,484.00 Depth: Slab Sawing and Removal of two trenches (1) 150'x6' and (1) 135' x 6', Concrete is based on being 6" thick. All Sawing and Removal to be done in one mobilization. 2 CORE DRILLING Diameter: 125.00 EACH 250.00 Depth: Core Drilling (2) 8" holes in 6" paving price is per hole. Work is based on being completed at the same time as saw cutting and demo. If work is done in a separate mobilization price will be a min charge of $550. 9,734.00 Exclusions: Layout of any sawing, trench covers, access, permits, water control, dust control, barricading, traffic control, escorting, breaking, protection of any properties, damage to any unmarked utilities, final cleanup of work area and concrete pour back. TERMS: DUE UPON RECEIPT / A 1.5% PER MONTH (18% PER ANNUM) SERVICE CHARGE WILL BE ADDED TO PAST DUE INVOICES WE ASSUME NO RESPONSIBILITY FOR LAYOUT "* Invoices calculated at measured quantities. ASSUMPTIONS: UNLESS OTHERWISE NOTED, CUSTOMER IS RESPONSIBLE TO PROVIDE: - Clean work area free of any obstructions. - Water control (including clean-up) or any protection of property. - Lift or scaffolding. IT IS EXPRESSLY AGREED AND UNDERSTOOD THAT ATI IS NOT RESPONSIBLE FOR: - Traffic control, purchase or pulling of any permits - Any damage to buried structures, utilities or post tension cables. - Barricading openings or safeguarding work performed. Printed: 08/07/2020 01:46:32 PM www.aggregatetechnologies.com Page 1 of 2 • - BcMAIN Bid Proposal for Baytown - Drain Pipe Amendment #13 PEPPER LAWSON WATERWORKS LLC 3701 KIRBY DR #1133 HOUSTON, TX 77098 Sales Representative Greg Arentz (M) 210-379-7606 (T) 210-657-1632 (F) 210-657-2321 Greg.Arentz@coreandmain.com Job Baytown - Drain Pipe Amendment #13 Bid Date: 07/07/2020 Bid #: 1402543 Core & Main 7620 Grissom Rd San Antonio, TX 78251 (T) 210-684-1150 07/06/2020 - 9:12 PM Actual taxes may vary Page 1 of 2 Bid Proposal for Baytown - Drain Pipe Amendment #13 PEPPER LAWSON WATERWORKS LLC Bid Date: 07/07/2020 Core & Main 1402543 Seq# Qty Description Core & Main 7620 Grissom Rd San Antonio, TX 78251 Phone:210-684-1150 Fax: 210-684-5521 Units Price Ext Price 60 LOADING DOCK TYPE A 70 168 18 PVC SDR26 HW SWR PIPE (G) 14' FT 4.45 747.60 80 2 18 HW SWR SDR26 45 GXG EA 71.53 143.06 90 12 1 LINK SEAL LS-475-SS EA 15.91 190.92 (12) LINK F/8" HW IN 12 HOLE 120 CHEM CONTAINMENT DRAIN 130 392 8 PVC SDR26 HW SWR PIPE G 14' FT 4.45 1,744.40 140 1 8 PRESS -SEAL BOOT F/CONC MH EA 55.00 55.00 160 6 8 HW SWR SDR26 45 GXG EA 71.53 429.18 170 2 8X8 HW SWR SDR26 WYE GXG EA 129.88 259.76 190 2 8 SDR35 CLEANOUT ADPT HXF L/PL EA 1 61.58 123.16 200 2 8 PVC SWR CLEANOUT PLUG MIPT EA 44.93 89.86 220 1 1 12X8 HW SWR SDR26 WYE GXG EA 339.59 339.59 230 2 12 PVC SDR35 SWR SPIGOT PLUG EA 86.10 172.20 Sub Total 4,734.85 Tax 0.00 Total Branch Terms: 4 294 73 UNLESS OTHERWISE SPECIFIED HEREIN, PRICES QUOTED ARE VALID IF ACCEPTED BY CUSTOMER AND PRODUCTS ARE RELEASED BY CUSTOMER FOR MANUFACTURE WITHIN THIRTY (30) CALENDAR DAYS FROM THE DATE OF THIS QUOTATION. CORE & MAIN LP RESERVES THE RIGHT TO INCREASE PRICES UPON THIRTY (30) CALENDAR DAYS' NOTICE TO ADDRESS FACTORS, INCLUDING BUT NOT LIMITED TO, GOVERNMENT REGULATIONS, TARIFFS, TRANSPORTATION, FUEL AND RAW MATERIAL COSTS. DELIVERY WILL COMMENCE BASED UPON MANUFACTURER LEAD TIMES. ANY MATERIAL DELIVERIES DELAYED BEYOND MANUFACTURER LEAD TIMES MAY BE SUBJECT TO PRICE INCREASES AND/OR APPLICABLE STORAGE FEES. THIS BID PROPOSAL IS CONTINGENT UPON BUYER'S ACCEPTANCE OF SELLER'S TERMS AND CONDITIONS OF SALE, AS MODIFIED FROM TIME TO TIME, WHICH CAN BE FOUND AT. https://coreandmain.com/TandC/ 07/06/2020 - 9:12 PM Actual taxes may vary Page 2 of 2 I & A CONSTRUCTION 19691 Lazy Lane Porter, Tx 77365 Tel: 832-752-2859 Fax: 281-987-2025 ribarraconstruction@vahoo.com July 7, 2020 To whom it may concern, I&A Construction proposes to Prep and Pour (Labor & Material) the following areas at the BAWA 6 MGD Surface Water Treatment Plant Project in Baytown, TX: First item removed Speonbill Way (Approx. 3?lsf @ $j19.99-a- square -€oe - - during latest revision Loading Dock (Approx. 972sf @ $10.00 a square foot) = $9,720.00 Containment Area (Approx. 834sf @ $10.00 a square foot) = $8,340.00 Total Proposal Price: $? "^ 00 18,060 This proposal excludes the following items: Electrical Power for Vibrators Formwork Systems Curing Compound Material & Labor Concrete Pump Truck and Hose I&A will provide full insurance and workers compensation for all employees. Thank You for this opportunity. Please feel free to contact me if you have any questions or concerns. We look forward hearing back from you. Best Regards, Refugio Ibarra I&A Construction Ptw waterworks July 7, 2020 Mrs. Andrea Brinkley Assistant Director Baytown Area Water Authority The City of Baytown 2401 Market St. Baytown, TX 77520 Re: CPR No. 75 BAWA 6 MGD Surface BAWA Job No. 1806021 Mrs. Brinkley, Please see attached proposal for shunt trip breaker and disconnect in order to meet code for elevator inspection. This change will result in a increase in the amount of $4,120.38. Please feel free to contact me at (713) 301-8637 with any questions or concerns. Regards, PLW Waterworks Katy Drown Project Manager Page 1 Baytown Area Water Authority BAWA 6 l%IGD Surface Water Treatment Plant BAWA Job No. 1806021 Elevator Disconnect Scone of Work Shunt Trip Disconnect for Elevator CPR No.: #075 Date: 07/07/20 PLW Job No.: PH Non -Taxed Labor Material Subcontract Taxed Nlat'I/E ui Unit Total Unit Total Unit Total Unit Total Item No. Description Qty Unit Cost Cost Cost Cost Cost Cost Cost Cost 1 Disconnect Required to meet NFPA Code 1 1 Advantage 1 LS S s s $ S 2,12700 $ 2 12700 $ s 22 P&S I LS S s S s S 1,35158 S 1 351 58 $ S Direct Cost Subtotal 3.47858 Small Tools a 5.0% n/a - n/a n/a Equipment Burden Q 50.0 % n/a n/a n/a n/a Tax Ot 8.25 % n/a n/a n/a Subtotal 2 3 478 58 Overhead & Profit 0 15.0 0 521 79 Subtotal 3 4.00037 Bonds & Insurance n 3.0% 12001 Subtotal 4 4 12038 Total of all columns 4 12038 Other Grand Total Cost 4,120.38 Page 2 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 PFEIFFER&SON, LTD. Electrical & Telecommunication Contractors PFEIFFER AND SON JOB # 4200119 CHANGE ORDER REQUEST Date: 6/23/2020 Project: BAWA 6MGD SWTP Description: Installation of Shunt Trip Disconnect for Elevator General Labor Supervisory Labor Subtotal items 1 and 2 Labor Burden 55% x Item 3 Cost of Materials Equipment Cost of Transportation Subcontractor Subtotal items 3,4,5,E and 7 Cost of Insurance 4% x item 8 Cost of Bonds (7.4.2.2.4) Subtotal lines 8,9 and 10 Overhead 10% Profit 5% Not Used Total change order amount items, items 11,12,13 and 14 Page 1 8.00 hours x $ 29.9 239.20 1.00 hours x $ 55.0 55.00 9QA 7n 161.81 578.00 65.00 0.00 0.00 1,099.01 43.96 32.32 1,175.29 117.53 58.76 0.00 $ 1,351.58 ti INTERESTS INCORPORATED F= P20111IMM 1 I SECUPM I SY.STM4 R?fBGRAM 7840 West Little York Phone: (713) 983-7253 Houston, Texas 77040 Fax: (713) 983-7292 Web: www.advantagefireprotection.com cbrvson0advantagefireprotection.com PROJECT CORRESPONDENCE (External) TO: PLW Waterworks Project No. 18-092 5359 E. Grand Parkway S. Baytown, TX 77523 Date: June 23, 2020 ATTN: Joseph Tocci PROJECT: BAWA Plant SUBJECT: Change Request 4 (CR004-R00) Fire Alarm / Elevator Shunt Trip Breaker Advantage Interests is pleased to offer for your consideration the following change request proposal for the above referenced project. Our proposal is outlined in the following sections: I. Bill of Material II. Scope of Work III. Exclusions IV. General Terms and Conditions Thank you for the opportunity to provide quality equipment and services for your fire protection needs. If you have any questions or require additional information, please do not hesitate to call. Respectfully, Craig Bryson Account Manager Accepted by: Page l of 2 Date: I. BILL OF MATERIAL 1. Fire Alarm System Description 1 ea Power Supply 1 ea Addressable Relay Module 2 ea Addressable Monitor Module 1 ea Control Relay, DPDT l0A Contacts 1 lot Programming 1 lot Installation Labor and Materials Our price for this scope of work is: $2,127.00 II. SCOPE OF WORK 1.1 Provide and install equipment and devices to interface the fire alarm system with the elevator shunt trip breaker. 1.2 Provide and install approximately 20 feet '.a" EMT conduit and wire for connection to the fire alarm system. 1.3 Provide programming, final test and addition to as -built plans. III. EXCLUSIONS 1.1 Providing and installing 120vac to the power supply. 1.2 Providing, installing and terminating circuit to shunt trip breaker. We are providing a relay as a point of connection for the electrician. IV. GENERAL TERMS and CONDITIONS 1 Delivery Point 1.1 The delivery point shall be F.O.B. Jobsite. 2 Terms of Payment 2.1 Terms are net 30 days from invoice date. 3 Taxes 3.1 Taxes on materials and labor are not included. The project is tax exempt. I(AMM-0, Page 2 of 2 SUPPLEMENT 2 Interfacing Fire Alarm Systems and Elevator Controls Bruce Fraser SimplexGrinnell, L.P. Editor's Note: The relationship between fire alarm s)stems and elevator control s_ystents, and hose these sYs►eins interface with each other, has had a long history, one that is still evolving. This supplement summarizes the historical development of these relationships and provides insight into the requirements for firefighters' recall and elevator shutdown. HISTORICAL PERSPECTIVE OF FIREFIGHTERS' RECALL AND ELEVATOR SHUTDOWN Background Safe operation of elevators has always been paramount to the elevator industry. In the late 1960s and early 1970s, attention was drawn to the impact of fire on elevator safety. Thought was given to human behavioral actions as well as the electrical and mechanical aspects. In a high-rise building fire, for instance, passengers overcrowding an elevator in their panic to leave the building might disable an elevator, or the elevator might actually be called to the fire floor by the actuation of a call button that has shorted or by one that reacts to heat. People unaware of the fire condition on an upper floor might continue to use the elevators to access the building. It was generally agreed that because of the various unsafe conditions faced by building occupants using elevators during a tire, it was important to prevent those occupants and visitors of the building from using elevators during a fire. It was believed that the safer option was for everyone physically capable of using the stairs to exit the building to do so. This strategy would also make elevators available to firefighters for stag- ing their equipment on Floors closer to the fire floor and for evacuating those individuals incapable of self -rescue. Conflicting Codes Many individuals who must deal with the coordination of building codes and standards understand that it is difficult to keep the building, elevator, sprinkler, and fire alarm codes in step with each other — initially because of a general lack of coordination between the various code com- mittees. Today, there is a concerted effort for cooperation with the code -making bodies and the fire services. Still, it Bruce Fraser of SimplexGrinnell in Westminster, Massachusetts, is a member of the Technical Correlat- ing Committee on Signaling Systems for the Protection of Life and Property. He also serves as a member of the NFPA Technical Committees on Supervising Station Fire Alarm Systems, Safety to Life, Building Code, Telecommunications, Clean Rooms, and Premises Security. In addition, Mr. Fraser is a member of ASME A17.1 Safety Code for Elevators and Escalators. Emergency Operations Committee. 721 722 Supplement 2 • Interfacing Fire Alarm Systems and Elevator Controls is easy to get out of sync because of the differences in code cycles and the edition dates of the various codes that jurisdictions adopt. For instance, NFPA 72 w, National Fire Alarm Code4, has operated on a 3-year cycle (e.g., 1996, 1999, 2002, 2007; the exception being from 2002 to 2007), whereas ASME A17.1, Safety Code for Elevators and Es- calators, has operated on a multiple -year code cycle with published yearly addenda or supplements that can be adopted by jurisdictions (e.g., 2000, 2002[a], 2003[b], 2004, 2005[a]. 2005[S]). ASME A17.1, 2004 edition, is the 17th edition of the Safety Code for Elevators and Esca- lators; its current supplement was issued on August 12, 2005, and is referenced as ASME A17.11S], 2005 supple- ment, which was effective as of February 12, 2006. Firefighters' Recall Introduced In 1973, ASME A 17.1 b, Supplement to the 1971 Elevator Code, introduced a new rule (Rule 211.3) that contained, among other things, a requirement for "Firefighters' Re- call." The new rule applied to all automatic non -designated attendant elevators that traveled 25 ft above or below the designated level. Elevators having to comply with ASME A 17.1 were now required to be "recalled" to a specific "designated" floor upon actuation of either a "3-position, key switch" (manual recall), or by smoke detectors located in elevator lobbies (automatic recall). The designated floor was usually the ground floor because that was usually the location where first -arriving firefighters entered the build- ing to evaluate the situation. Firefighters were to be the only individuals to have access to the keys for the 3-position key switch. They would use this feature to capture and gain control over the elevator(s) for their use in fire fighting and assisting those not capable of evacuating on their own. During this time period, smoke detectors were not nearly as reliable and stable as they are today and the industry was plagued with unnecessary smoke detector actuations and recalled elevators. In the 1970s, smoking was not frowned upon or prohibited in buildings as is the common practice today. Ashtrays were often placed right tinder or in close proximity to the elevator lobby smoke detectors. Passengers would take their last puff and deposit their smoking material in the ashtray prior to boarding the elevator — that last puff often led to trash in the ashtray igniting and a quick ride down to the designated level! ASME A 17.1, 1981 edition, introduced recall of eleva- tors to an "alternate" level. This requirement called for a smoke detector in the main lobby to cause recall to an alternate level (other than the designated floor). Also intro- duced was a new requirement for smoke detectors in the elevator machine room to recall the elevators to the "desig- nated" floor. ASME A17.1, 1984 edition, produced the requirement that only the elevator lobby and the elevator machine room smoke detectors were to be used to automatically recall elevators. During this time, smoke detectors had no specific in- stallation requirements other than ASME A] 7.1 referenc- ing that smoke detectors be installed in accordance with NFPA 72E, Automatic Fire Detectors. Chapter 4. Smoke detection technology was still in its relatively early stages, so the building owners continued to experience difficulties with instances of elevators returning (being recalled) as a result of unwarranted smoke detector actuation. These events were responsible for a groundswell reaction from building owners to disconnect the recall function, and it also led to installation of systems with questionable relia- bility. Various configurations of smoke detectors were being installed using different wiring methods and even intermixing of single station smoke alarms and system smoke detectors. Coordination between electrical contrac- tors and elevator contractors didn't happen on a regular basis, and installation guidance was sorely lacking. NFPA's Involvement NFPA's first mention of smoke detectors used for firefight- ers' recall appeared in the 1987 edition of NFPA 72A, htstallation, Maintenance and Use of Local Protective Sig- naling Systems. The section was titled "Elevator Recall for Firefighters' Service," and it required that smoke detectors located in elevator lobbies and elevator machine rooms used to initiate firefighters' service recall be connected to the building fire alann system. And, unless otherwise permitted by the authority having jurisdiction, only those detectors could be used to recall the elevators. The feeling was that as long as the elevators were not in danger from fire (as determined by elevator lobby and machine room smoke detectors), they could continue to operate for use of building occupants. And, of course, the other reason was that there would be less risk of incurring nuisance alarms that would be disruptive to building occupants and bad public relations for the building owner. The actuated detector, in addition to initiating recall, was required to initiate an alarm condition on the fire alarm system and annunciate the zone from which the alarm originated. Both acceptance testing and periodic testing were per- formed in accordance with requirements in NFPA 72E, 1987 edition, and NFPA 72H, Testing Procedures for Local, Auxiliary, Remote Station, and Proprietary Protective Sig- naling Systems, 1988 edition. NFPA 72A, 1987 edition, also required that for each group of elevators within the building, two elevator zone 2007 National Fire Alarm Code Handbook Supplement 2 • Interfacing Fire Alarm Systems and Elevator Controls 723 circuits be terminated at the elevator controller. The opera- tion had to be in accordance with ANSUASME A 17.1 Rules 21L3--211.8. Essentially, the smoke detector in the designated lobby of recall would actuate the first circuit, and the smoke detectors in the remaining lobbies and eleva- tor machine room would actuate the second circuit. The reason for the two circuits was to be able to differentiate the signal coming from the smoke detector at the designated elevator landing from all the other smoke detectors at the other elevator lobbies and elevator machine room. If that detector at the designated level actuated, it would be indica- tive of fire conditions in that area, so the elevators would then be recalled to an "alternate' level. The "alternate" level would be determined at the discretion of the authority having jurisdiction (usually the local fire department). Smoke detectors for elevator recall were also required to initiate an alarm even with all other initiating devices on the circuit in an alarm state. The reason for this require- ment was to ensure the reliability of the recall operation because some fire alarm initiating device circuits could not support having all devices in alarm at one time and still guarantee the smoke detector used for elevator recall would operate. Two examples (drawings) were placed in the appendix of NFPA 72A recommending wiring configuration for the smoke detectors for a new installation as well as for an elevator retrofit situation. The standards at this time did not require electrical supervision of these control circuits. In 1989, ASME A17.1b addressed smoke detectors in hoistways. Smoke detectors were allowed to be installed in any hoistway, but they were required to be installed in hoistways that were sprinklered. The hoistway smoke detectors, when actuated, were to cause recall to the desig- nated level. Also, the elevators must react only to the first recall signal. In other words, if the detector at the desig- nated level actuated and then shortly after the third floor elevator lobby detector actuated, the car would be recalled to the alternate floor of recall and not the designated level because the detector at the designated level was the first to actuate. This requirement was added because it was believed that the first detector to operate would have a high probability of sensing a fire in its vicinity, whereas there would be a fair chance of the smoke migrating to other locations and tripping the detectors and giving conflicting instructions to the elevator controllers. In 1990, NFPA consolidated some of the signaling standards (NFPA 72A, Installation, Maintenance, and Use of Local Protective Signaling Systems, 1987 edition; NFPA 7213, Auxiliary Protective Signaling Systems for Fire Alarm Service, 1986 edition; NFPA 72C, Remote Station Protec- tive Signaling Svstens, 1986 edition; NFPA 72D, Proprie- tary Protective Signaling Systems, 1986 edition; and NFPA National Fire Alarm Code Handbook 2007 72F, Installation, Maintenance and Use of Emergency Voice/Alarm Communication Systetns, 1985 edition), into a single publication, NFPA 72, Installation, Maintenance, and Use of Protective Signaling Systems, 1990 edition. There were no changes made to the paragraphs relating to elevators in NFPA 72A, 1987 edition. The ASME A 17.1, 1990 edition, added a requirement for all elevator cars to be provided with an illuminated visual and audible signal system (frefighter's helmet sym- bol). The light would illuminate during recall to alert pas- sengers that the car is returning nonstop to the designated level. In reality, unless passengers were taught or otherwise shown what the light meant, it was doubtful as to the value this feature provided the average elevator passenger. Exhibit S2.1 shows an illustration of the firefighter's hel- met symbol. Later, this visual symbol will be discussed in another application. ■■■■■■■■■■■ a■n� ■■■■■■■■■■■ i■■■■■�. ■w■/i■■■\■■■■■/�■■■\�■■\ L■ra.■■■i:�■ l■�5ii•ii:S� ■■■■■■■■■■■ M■■■■■Ht General note: Grid is for scaling purposes only. Fig. 2.27.3.1.6(h) VISUAL SIGNAL EXHIBIT S2.1 Firefighter's Helmet Symbol. (Reprinted from ASME A17. la, 2005, by permission of the American Society of Mechanical Engineers. All rights reserved.) The 25 ft travel criterion was dropped from ASME A17.1b, 1992 supplement, so the Firefighters' Service Re- call then applied to all automatic non -designated attendant elevators regardless of the travel distance. ASME A17.1 [1993] (14th Edition) In 1993 liaisons between the NFPA 72 Technical Commit- tee on Protected Premises Fire Alarm Systems and the ASME A 17.1 Emergency Operations Committee were es- tablished and were effectively communicating to coordi- nate their code activities. Requirements were more complex, and it was essential this communication and co- operation continue. More specific application details were surfacing, such as the requirement that smoke detectors in the hoistway might be installed below the lowest recall level and when actuated, those detectors would now cause the elevator car to be sent to the upper level of recall. Reasoning for that change was to keep the car away from the fire. 724 Supplement 2 • Interfacing Fire Alarm Systems and Elevator Controls NFPA 72 Changes [1993] In 1993 NFPA further consolidated the signaling standards to form what is now NFPA 72, National Fire Alarm Code. Reference to hoistway smoke detectors was added in this edition to correlate with ASME A17.1, 1990 edition. The result required hoistway detectors to cause recall of eleva- tors to the designated level. The 1993 edition of NFPA 72 also, for the first time, addressed elevator recall in buildings that were not required to have a fire alarm system. Those buildings having eleva- tors and no building fire alarm systems and having to comply with ANSI/ASME A 17.1 must now have an "Ele- vator Recall and Supervisory Panel." This panel is essen- tially a fire alarm control unit (now defined as a "dedicated function fire alarm control unit") specifically used to pro- vide signals to the elevator controller to initiate elevator recall, but not notify the occupants of the building or the fire department. Additionally, this control unit was used to initiate removal of elevator main line power prior to sprinkler operation should the building have sprinklers in the elevator machine room or hoistway. The main reason for this requirement was to ensure these critical elevator recall systems were installed with the reliability of building fire alarm systems, which included the supervision (moni- toring for the integrity) of circuit wiring and secondary power meeting the requirements of NFPA 72. Also in the 1993 edition, the term fire safety, control fiaictions was introduced. The section on fire safety control functions addressed those components and interfaces that are meant to increase the level of life safety and property protection in buildings. The following are examples of such fire safety control functions: door holding, door re- leasing, door unlocking, elevator recall, shunt trip, fan control, smoke hatches, and stairway ventilation. The sec- tion on fire safety control functions reinforced the require- ment that the circuits from the fire alarm system to the elevator controller(s) had to be monitored for integrity. A section on shutdown of main elevator power was also added in the 1993 edition of NFPA 72 primarily as a result of the ASME 17.1 requirements that now addressed the concerns of sprinklers in elevator machine rooms and hoistways. These sprinkler requirements were driven by national building codes. This subject is discussed in greater detail later under the topic "Main Line Power Disconnect -- Shunt Trip." ASME A17.1 b [1995] ASME A 17.1 b, 1995 supplement, included a new require- ment addressing the condition (as with many hydraulic elevators) where the elevator machine room is on the desig- nated level. Smoke detectors in the elevator machine room, when actuated, will send the car to the alternate level. Again, the reasoning was to use the recall level furthest from the fire condition. NFPA 72 Changes [1996] In the 1996 edition of NFPA 72, smoke detectors in hoistways were prohibited unless the top of the hoistway had a sprinkler. If the top of the hoistway was sprinklered. then ASME A17.1b, 1995 supplement, required a smoke detector to be installed to initiate recall prior to having the main line power shut down. The reason for not wanting smoke detectors in hoistways is obvious. The adverse environmental condi- tions of most elevator hoistways, with dirt and contami- nants and varying air velocities caused by elevator piston action, initiated many unwarranted or "nuisance" recalls. Because smoke detectors in hoistways were (and still are) difficult to service and to perform periodic testing on, smoke detectors were often sadly neglected, allowing them to become dirty, overly sensitive, and prone to causing nuisance recalls. Another section added to the 1996 edition of NFPA 72 allowed other appropriate automatic fire detection to be used in place of smoke detectors in those situations where the environment was unsuitable for smoke detectors, such as unheated elevator lobbies commonly found in northern climates. A "third" control circuit was added to the existing "designated" floor of recall and "alternate" floor of recall circuits. This third circuit was to operate when a hoistway or machine room smoke detector actuated. It was to annun- ciate separately at the fire alarm control unit and other required annunciators. The purpose was to alert firefighters and other emergency personnel of a potential problem that might cause unsafe elevator operation and, indeed, they may soon lose elevator power. At this time there was confusion in the industry be- cause ASME A 17.1 had not yet introduced the third circuit as an elevator requirement. In the works was a proposal to ASME A 17.1 that would cause the firefighter's helmet symbol in the elevator car to flash to indicate impending danger if firefighters were to continue to use the car under "Phase II — Emergency In -car Operation." Under "Phase II," the elevator is controlled by firefighters by way of a special key that permits firefighters to override other safety controls. The firefighters can then use the elevator for staging their equipment and for evacuating people. ASME A17.1a [1997] Some fairly substantial changes were made in terminology in the 1997 supplement of ASME A17.1. The title of sec- 2007 National Fire Alarm Code Handbook Supplement 2 • Interfacing Fire Alarm Systems and Elevator Controls 725 tion "211.3b Smoke Detectors" was changed to "211.3b Phase 1 Fire Alarm Activation." Also, the term fire alarrn initiating devices replaced the previously used term smoke detectors. This change was intended to recognize that smoke detectors may not be the most appropriate choice of detection to initiate elevator recall when environmental conditions exceed those for which the smoke detector is suitable. ASME Al7.1 b [1998] A new paragraph was added to the 1998 supplement of ASME A17.1 requiring that the actuation of a fire alarm initiating device in the elevator machine room or in the hoistway cause the visual signal (firefighter's helmet) in the affected elevator car to flash. This addition provided the change needed for correlation with the "third circuit" requirement added in the 1996 edition of NFPA 72. NFPA 72 Changes [1999] There were no substantive changes related to elevator recall in the 1999 edition of NFPA 72. See changes to power disconnect requirements later in the section on "Elevator Shutdown and Sprinklers." ASME A17.1 [2000] (16th Edition) The 2000 edition of ASME A 17.1 was harmonized with the Canadian CAN/CSA B44 Elevator Safety Standard. In addition, the entire code was reformatted and renumbered using a decimal numbering system. Some heading changes were made, for instance. "Fire- fighters' Service — Automatic Elevators" was changed to "Firefighters' Emergency Operation — Automatic Eleva- tors." And, "Phase I Fire Alarm Activation" was changed to "Phase I Emergency Recall Operation by Fire Alarm Initiating Devices." But, the content did not change essen- tially. Some rewording and paragraph modifications were made to accommodate the differences that still exist be- tween the United States and Canada. Where differences exist between ASME A17.1 and CAN/CSA B44, there is wording such as "7n jurisdictions not enforcing the NBCC . . . ". The NBCC refers to the National Building Code of Canada, so used in that context, that particular code requirement would apply to the United States. NFPA 72 Changes [2002] Several correlation changes occurred in the 2002 edition of NFPA 72. Wording was added to include consideration for new elevator technology that alters the way we have traditionally thought of elevators. Various elevator compo- nents and equipment (drive motors, controllers, braking National Fire Alarm Code Handbook 2007 mechanisms, etc.) were customarily installed in spaces called machine rooms. Recent elevator technology has led to what is now referred to as "machine room -less" elevator systems. Some elevators today have the equipment in other spaces, such as mounted on the elevator car itself. So, now, when referring to locations where smoke detectors are installed for the purpose of initiating recall (elevator lob- bies, elevator hoistways, and elevator machine rooms), additional reference is made to elevator machine rooms "'including machine space, control room, and control space." Where NFPA 72, 1999 edition, addressed three sepa- rate circuits per each group of elevators within a building for the purpose of interfacing the fire alarm system with the elevator system, NFPA 72, 2002 edition, addressed the potential of having more than three circuits. Wording was changed from "three separate elevator control circuits" to "a minimum of three separate elevator control circuits." The reason for that change was that in some instances, two (or more) separate hoistways could share the same common elevator machine room. An ASME A] 7.1 requirement is to provide a danger signal to elevator cars (by flashing the firefighter helmet symbol) if there is fire in an elevator hoistway or an elevator machine room. The reasoning be- hind the change was that if the fire was in one hoistway, the signal should not be given to the elevator car in the other hoistway where there may be no immediate danger. Of course, if the fire occurred in the common machine room, the signal would be sent to the cars in both hoistways. Annex material was added to advise against installing smoke detectors in outdoor locations or locations that are exposed to weather, such as unenclosed elevator lobbies in open parking structures, because those environments can exceed the parameters of detector listing and further could result in unwanted alarms and unnecessary recall of elevators. If a smoke detector has undergone testing and subsequent listing as acceptable for the anticipated environ- ment, then, of course, that device would be appropriate for installation in that case. ASME A17.1a [2002] Supplement There were no changes in requirements to the emergency recall operation in this first addendum to the 2000 edition of ASME A 17.1. ASME A17.1 b [2003] Supplement There were no substantive changes in requirements for emergency recall, but wording was modified to reaffirm the intent of where fire alarm initiating devices used for the purpose of initiating emergency recall were to be in- stalled. The fire alarm initiating devices were required to 726 Supplement 2 • Interfacing Fire Alarm Systems and Elevator Controls be installed in conformance with NFPA 72 and located as follows: (1) at each floor served by the elevator; (2) in the associated elevator machine room; and (3) in the elevator hoistway, when sprinklers are located in those hoistways. ASME A17.1 [2004] 17th Edition No new requirements were introduced to the existing emer- gency recall requirements. ASME A17.1a [2005] Supplement No new requirements were introduced to the existing emer- gency recall requirements. ASME A17A S [2005] "Special" Supplement This release is a "special" supplement that was published as a result of an ad hoc committee tasked with addressing the issues associated with the advancement of new techno- logies being used in today's design and construction of elevator equipment. The committee looked at the various safety aspects of the new equipment and its installation, and recommendations were put forth in proposals that ad- dressed equipment located in traditional hoistways and machine rooms as well as what is now termed "machinery spaces, control spaces" that may be found either inside or outside the hoistway. No new requirements were introduced to the existing emergency recall requirements. NFPA 72 Changes [2007] A significant rewrite of some of the paragraphs of the Elevator Recall for Firefighters' Service section was made with the intent of improving clarity, readability. and conti- nuity. The section is now arranged with general requirements leading in to three distinct sections specific to the output signals from the fire alarm system to the elevator control system, namely, Designated Level Recall, Alternate Level Recall, and Visual Warning. ELEVATOR SHUTDOWN AND SPRINKLERS Since its inception, the requirement in ASME A17.1 for shutdown of elevator main line power has been the cause for confusion in the industry and also has been very contro- versial. The following paragraphs try to provide some back- ground and insight on the subject. Main Line Power Disconnect — "Shunt Trip" Main line power disconnect, commonly referred to as "shunt trip." was first required by ASME A17.1, 1984 edition. The reference to "shunt trip" is used because it is that method that is predominantly used to disconnect the elevator main line power. When the term main line power is used here, it does not mean '*complete" or "total" power. It means the power that drives the elevator itself. Those circuits that would not be shut down would include the following: • Branch circuits for car lighting, receptacle(s), ventila- tion, heating, and air conditioning • Branch circuit for machine room/machinery space lighting and receptacle(s) • Branch circuit for hoistway pit lighting and recepta- cle(s) Because of the potential danger from water shorting and bridging electrical components and because it is con- sidered hazardous to have water on the elevator brake (braking system) of traction elevators, especially when the car is in motion, the requirement to disconnect the elevator main line power prior to the release of water from the sprinkler system was included in ASME 17.1. 1984 edition. The concept was to remove main line power from the elevator to stop the car and prevent it from moving prior to a sprinkler releasing water that could get onto elevator electrical components or the elevator brake. There was a concern that "shorting" of control and safety circuits could result in dangerous situations such as uncontrollable mo- tion and running of the elevator with doors open, and so on. On traction elevators there is the additional concern of getting water on the brake while the car is moving, which could result in uncontrolled braking and failure to stop safely. The original theory for elevator shutdown was to use a heat detector as the means to actuate shunt trip. The following sequence was intended: 1. A smoke detector used for elevator recall would sense smoke and initiate recall. 2. The elevators would be recalled immediately (with or without passengers) to the floor of recall and doors open. 3. Heat buildup causes heat detector to actuate, which initiates main line power shutdown. 4. Power is removed from elevator and the car cannot be used until power is manually restored. 5. Further heat buildup causes sprinkler to fuse, releasing water to control fire. In ASME A 17.1 a, 1994 supplement, the wording changed to "upon or prior to the application of water from sprinklers." Effectively, the rewording now allowed sprinkler waterflow switches to initiate main line power disconnect in addition to the previously used heat detectors. Built-in delays were not allowed in the waterflow switch 2007 National Fire Alarm Code Handbook Supplement 2 • Interfacing Fire Alarm Systems and Elevator Controls 727 (such as the retard mechanism furnished with many flow switches that could be set to provide as much as a 90 second delay in initiating a signal). The reason flow switches are provided with built-in delays is to prevent false tripping from "water hammer" caused by changes in pressure in the water supply. At this time, the heat detector appeared to be the most widely used as well as preferred option because waterflow switches (without retard mechanisms) were prone to causing unwanted and unwarranted recall of elevators. Today, the use of more reliable check valves has minimized this problem. Power Disconnect Initiated from the Fire Alarm System Confusion existed for years over a couple of code sections, one on a sentence in earlier editions of the National Electri- cal Code'", Article 620 (Elevators), under the section cov- ering "Disconnecting Means and Control." It stated that ..nor shall circuit breakers be opened automatically by a fire alarm system." Some interpreted this as a requirement that the heat detector used to actuate shunt trip could not be associated with or connected to the fire alarm system. In fact, what was intended was that the elevator power should not be shut down when the fire alarm system was activated by just any fire alarm initiating device in the building. Many were not aware of the programming capa- bilities that fire alarm systems have that allow for matrixing of various inputs and outputs. So, for years, a separate circuit, not connected to the fire alarm system, was com- monly used to accomplish elevator main line power discon- nect. Unfortunately, much of the time the circuit conductors were not monitored for integrity (supervised). This over- sight meant that a broken wire or open circuit could go undetected until testing revealed the problem and also meant the circuit could be out of commission when needed in an emergency. These instances emphasize the need for critical circuits to be monitored for integrity, as is the case with fire alarm initiating device circuits. In the 1993 edition of NFPA 70, National Electrical Code, the troublesome reference to the fire alarm system was removed to avoid the confusion. The requirements regarding the means to achieve elevator shutdown were also more clearly defined in NFPA 72 119931. j. If heat detec- tors were used to shut down elevator power prior to sprin- kler operation, the heat detector was required to have a lower temperature rating and higher sensitivity when com- pared to the sprinkler. Obviously, in order to accomplish the desired sequence, the heat detector must actuate earlier than the sprinkler under the fire condition. If the sequence somehow occurred in reverse order, water could be released on live electrical components as well as on the braking National Fire Alarm Code Handbook 2007 mechanism, which is exactly the condition that is trying to be avoided. Heat detectors also had to be installed within 2 ft of each sprinkler head in the elevator machine room and hoistway. This spacing was to ensure the heat detector sampled, as nearly as practicable, the temperature that the sprinkler was sensing. The second area for confusion was a requirement in NFPA 72A, 1987 edition, htstallation, Maintenance and Use of'Local Protective Signaling Systems, under the sec- tion for "Installation and Design' that stated "The performance of automatic control functions shall not inter- fere with power for lighting or for operating elevators." This requirement remains in NFPA 72, 2007 edition, as paragraph 6.16.2.1. Elevator main line power shutdown is a fire safety control function, and the operation is intention- ally designed as such. This operation does not interfere with operating power for the elevators; it instead controls the power shutdown. NFPA 72 Elevator Shutdown (1999) A weak link in the reliability of "shunt trip" was recog- nized and addressed by NFPA 72, 1999 edition. It was often found during periodic testing of the shunt trip feature that the power needed to trip the shunt trip breaker was not available. This lack of power was usually because a circuit breaker that supplies the needed power was in the off position. The requirement for supervising that power was established in NFPA 72, 1999 edition. Absence of the power required a supervisory signal to be indicated at the fire alarm control unit and required annunciators. An example of a typical method of providing the elevator power shunt trip supervisory signal was included in the Appendix. NFPA 72 Elevator Shutdown (2002) In NFPA 72, 2002 edition, it was made clear that the initiating devices (heat detectors and flow switches) used to initiate main line power disconnect (shunt trip) are re- quired to be monitored for integrity by the fire alarm control unit. As mentioned previously, if the initiating devices were not connected to the fire alarm system, a broken wire, for instance, could disable the circuit and go unnoticed until found during periodic testing. This requirement increases the operational reliability of the circuit and helps to ensure the shunt trip feature will operate properly when called on in an emergency. ASME A17.1a [2005] Supplement In this supplement, wording was added to require that heat detectors and sprinkler flow switches used to initiate power removal comply with the requirements of NFPA 72. 728 Supplement 2 • Interfacing Fire Alarm Systems and Elevator Controls ASME Al7.1 S [2005] "Special" Supplement This special supplement included significant rewrites of certain chapters. Unfortunately, when a large modification is made to a code, there is the potential for something "slipping through the cracks" or the undoing of some previously coordinated efforts. The following issue may be cause for some confusion until it is addressed in a future edition. Previous editions of ASME A17.1 exempt the power removal requirements for sprinklers in the pit if the installa- tion complies with the NFPA 13 requirement for installa- tion of sprinklers at or less than 24 in. from the bottom of the pit. The new wording is in more of a performance language and makes the decision very subjective. A com- parison of the wording follows: Wording prior to Al7.IS [20051 ... . . means shall be provided to automatically dis- connect the main line power supply to the affected elevator upon or prior to the application of water from sprinklers located in the machine room or in the hoistway more than 24 inches above the pit floor." Wording of A17.IS 12005J ` . . . where elevator equipment is located or its enclo- sure is configured such that application of water from sprinklers could cause unsafe elevator operation, means shall be provided to automatically disconnect the main line power supply to the affected elevator upon or prior to the application of water." Note: there is no longer mention of sprinklers installed 24 inches or less from the bottom of the pit. Sprinklers and Fire Alarm Initiating Devices in Hoistways A review of the requirements of ASME A17.1, Safety Code for Elevators and Escalators; NFPA 72, National Fire Alarm Code; and NFPA 13, Standard for the Installation of Sprinkler Systems, considered collectively, would suggest that there may be no need to install fire alarm initiating devices for the purpose of initiating main line power dis- connect (shunt trip) in hoistways of passenger elevators. If the hoistway of a passenger elevator is noncombustible and the car enclosure materials meet the requirements of ASME A17.1 (which should be the case with all new elevator installations), then NFPA 13 does not require sprinklers at the top of the hoistway. Thus, with respect to requirements for the top of the hoistway, if the sprinkler is not needed, then the corresponding requirement for the smoke detector that would be used for recall goes away as well as the corresponding requirement for the heat detector used for power disconnect. Further, if the noncombustible elevator hoistway does not contain combustible hydraulic fluids, NFPA 13 does not require sprinklers at the bottom of the hoistway (discussed further below). If no sprinklers are installed anywhere in the hoistway (including the eleva- tor pit) then there is no requirement for initiating devices to be installed anywhere in the hoistway for either recall or shutdown. It is important to recognize that this applies to passenger elevators only and not to freight elevators. So, for freight elevators, the sprinkler at the top of the hoistway is still required and, therefore, so is the smoke detector (or other automatic initiating device), as well as the heat detector used for power disconnect. NFPA 13 requires sidewall spray sprinklers to be in- stalled at the bottom of each elevator hoistway not more than 0.61 in (2 ft) above the floor of the pit. However, there is an exemption for the sprinkler requirement for enclosed, noncombustible elevator shafts that do not con- tain combustible hydraulic fluids. Realistically, this exemp- tion is rarely observed and more than likely, sprinklers will be installed in elevator pits. In addition, the ASME A 17.1 2000 and 2004 codes and supplements ASME A 17.1 a 119971 through ASME A17.1a [2005] indicate that main line power disconnect is not required if those sprinklers are installed no more than 0.61 m (2 ft) from the floor of the pit. However, this prescriptive exemption has been replaced in ASME A 17.1 S [20051 Special Supplement with subjective language and not the clear exemption that earlier editions provided. (Refer to previous section ASME A I T I S [20051 "Special" Supplement for additional de- tails.) It is therefore extremely important to know what edition of ASME A17.1 is in force. In any event, current requirements for elevator recall initiated from the pit allow initiation from either a sprinkler waterflow device or from an automatic fire detection ini- tiating device (usually a heat detector). Maintaining a high degree of reliability for the fire alarm system is fundamental to the purpose of the National Fire Alarm Code. For that reason, paragraph 6.16.3.7 of the 2007 edition permits the use of other automatic fire detection devices where ambient conditions prevent the reliable use of smoke detectors. Elevator hoistways are often locations where ambient conditions exceed those for which the smoke detectors have been tested and listed. When automatic fire detection devices are needed within a hoistway, the selection of the devices must consider system reliability as well as the performance needed to provide the intended system operation. In summary, when sprinklers are installed in an eleva- tor hoistway (either at the top or bottom), appropriate auto- matic fire detection devices are required to provide elevator recall. (See 6.16.3.12.1 and 6.13.3.12.2 of the Code.) If any of these installed sprinklers are located more than 0.61 m (2 ft) from the floor of the pit (ASME A17.1a [2005] 2007 National Fire Alarm Code Handbook Supplement 2 • Interfacing Fire Alarm Systems and Elevator Controls 729 and earlier), or where elevator equipment is located or its enclosure is configured such that application of water from sprinklers (in any location) could cause unsafe elevator operation (ASME A 17.1 S 120051), appropriate automatic fire detection devices are required to provide power shut- down. Requirements for elevator shutdown are addressed separately from those for elevator recall, and ASME A 17.1 prohibits the use of smoke detectors for the purpose of power shutdown. It is worthwhile to note that main line elevator power shutdown is always required when sprin- klers are installed in the elevator machine room. Workshop on Emergency Use of Elevators In March 2004, a workshop co -sponsored by ASME, NFPA, NIST, ICC, iAFF, US Access Board, and others was held in Atlanta, Georgia, to consider the challenges of evacuation of high-rise buildings in fire and other emer- gencies. It was a three-day conference with over 120 life safety professionals attending from various communities concerned with high-rise safety and egress. There were two distinct focus points, one on the use of elevators by firefighters and one on the use of elevators for occupants during emergencies. The participants were split up into breakout groups to develop recommendations as to how elevators in high-rise buildings could be put to better use during emergencies. The goal was to develop proposals that could be submitted to various code -writing organiza- tions for consideration. A steering committee made up of all the sponsoring organizations reviewed the breakout groups' recommendations and formulated plans for the next steps to be taken and also to identify the appropriate standards -making bodies to which to direct the proposals. Some of the consistently repeating themes were as follows: • The culture change since 9-11 and the reluctance of occupants to stay in place and await further instruc- tions • Elevators not meant to be a substitute for stairs • Evacuation of people with mobility impairments • Water entering hoistways • Lack of firefighter confidence in using elevators • Entrapment caused by activation of shunt trip • Re-educating people to use elevators for egress after years of "don't use the elevators — use the stairs" instructions There were also repeating recommendations from the breakout groups such as mandatory adoption of ASME A17.3 everywhere; ensuring the reliability of Phase I and Phase II operation; better training of firefighters on elevator operation: enforcing the building emergency plan; sprin- klering all buildings; the need for "real-time" communica- National Fire Alarm Code Handbook 2007 tion to building occupants/emergency responders: and the use of compartmented and pressurized lobbies/vestibules. Consistent themes relative to the needed process in- cluded utilizing a risk/hazard analysis, involving firefight- ers in the decision making, and involving the appropriate committees (A 17.1, B44, model building and fire codes, and NFPA Codes and standards). The two active task groups resulting from the work- shop efforts (Task Group on the Use of Elevators by Fire- fighters and Task Group on the Use of Elevators for Occupant Egress) are perfonning comprehensive risk/ hazard analyses of various emergency scenarios plus the residual hazards and the mitigation of the hazards. The task groups have estimated completion sometime late 2007 to early 2008. The groups will then put forth their conclu- sions and outline their recommendations. The task groups, made up of various industry components (research, fire service, architect and engineering, codes and standards makers, disability interests, and other industry members), have embarked on a journey that will command a Hercu- lean effort. These efforts will most certainly culminate in a signifi- cant impact on the interface and interaction between sprin- kler, fire alarm, and elevator systems. CONCLUSION A historical perspective has been given here to help provide a better understanding of both the actual code evolution and some of the thought processes that went into the interface requirements for elevator and fire alarm systems. During the past decade it became very evident that the issues faced in addressing these challenges were ones that were not "black or white." There were, and continue to be, many varying shades of gray. One thing, though, is very clear. There is now a spirit of willingness and cooperation be- tween industry, code enforcement, and the fire service to continue to work together to find the best solutions to achieve the highest level of safety and reliability for the passengers and emergency personnel who use elevators. With more focus on improving building evacuation time by rethinking and improving the egress process, with per- formance -based design approaches, and with new technol- ogies providing more options, that cooperation will need to continue as we face even more difficult and challenging decisions ahead. REFERENCES ANSI A17.1 A, Safety Code for Elevators, 8th edition, American National Standards Institute, New York, NY, 1971. 730 Supplement 2 • Interfacing Fire Alarm Systems and Elevator Controls ANSI A17.1b, 1973 supplement to ANSI A17.1 A, Safety Code for Elevators, 8th edition, American National Standards Institute, New York, NY, 1971. ANSUASME A17.1, Safety Code for Elevators and Esca- lators, loth edition, ASME International. New York, NY, 1981. ANSI/ASME 17.1, Safety Code for Elevators and Escala- tors, IIth edition, ASME International, New York. NY, 1984. ANSI/ASME A17.1b, 1989 supplement to ANSI A17.1, Safety CodeforElevators and Escalators, 12thedition, ASME International, New York, NY, 1987. ASME A17.1. Safety Code for Elevators and Escalators, 13th edition, ASME International, New York, NY, 1990. ASME A 17.1 b, 1992 supplement to ANSI A 17.1, Safety Code for Elevators and Escalators, l3th edition, ASME International, New York, NY, 1990. ASME A 17.1 a, 1994 supplement to ANSI A 17.1, Safety Code for Elevators and Escalators, 14th edition, ASME International, New York, NY, 1993. ASME A 17.1 b, 1995 supplement to ANSI A 17.1, Safety Code for Elevators and Escalators, 14th edition, ASME International, New York, NY, 1993. ASME A 17.1 a, 1997 supplement to ANSI A 17.1, Safety Code for Elevators and Escalators, 15th edition, ASME International, New York, NY, 1996. ASME A 17.1 b, 1998 supplement to ANSI A 17.1, Safety Code for Elevators and Escalators, 15th edition, ASME International, New York, NY, 1996. ASME A 17.1. Safety Code for Elevators and Escalators, 16th edition, ASME International, New York, NY, 2000. ASME A 17.1 a, 2002 supplement to ANSI A 17.1, Safety Code for Elevators and Escalators, 16th edition, ASME International, New York, NY, 2000. ASME A 17.1 b, 2003 supplement to ANSI A 17.1, Safety Code for Elevators and Escalators, 16th edition, ASME International, New York, NY, 2000. ASME A17.1, Safety Code for Elevators and Escalators, 17th edition, ASME International, New York, NY, 2004. ASME A 17.1 a, 2005 supplement to ANSI A 17.1, Safety Code for Elevators and Escalators, 17th edition, ASME International, New York, NY, 2004. ASME A 17.1 S, 2005 special supplement to ANSI A 17.1, Safety Code for Elevators and Escalators, 17th edition, ASME International, New York, NY; 2004. CAN/CSA-1344, Safety Code for Elevators, Canadian Standards Association, Rexdale (Toronto), ON, Can- ada. NFPA 13, Standard for the Installation of Sprinkler Sys- tems, 2007 edition, National Fire Protection Associa- tion, Quincy, MA. NFPA 70, National Electrical Code R, 2005 edition, Na- tional Fire Protection Association, Quincy, MA. NFPA 72, National Fire Alarm Code, 2007 edition, Na- tional Fire Protection Association, Quincy, MA. NFPA 72"", National Fire Alarm Code",, 2002 edition, Na- tional Fire Protection Association, Quincy MA. NFPA 721�, National Fire Alarm CodeO, 1999 edition, Na- tional Fire Protection Association, Quincy, MA. NFPA 72s , National Fire Alarm CodeO, 1996 edition, Na- tional Fire Protection Association, Quincy, MA. NFPA 72'�, National Fire Alarm CodeO, 1993 edition, Na- tional Fire Protection Association, Quincy, MA. NFPA 72, Installation, Maintenance, and Use of Protective Signaling Systems, 1990 edition, National Fire Protec- tion Association, Quincy, MA. NFPA 72A, Installation, Maintenance and Use of Local Protective Signaling Systems, 1987 edition, National Fire Protection Association, Quincy, MA. NFPA 7213, Auxiliary Protective Signaling Systems for Fire Alarm Service, 1986 edition, National Fire Protection Association, Quincy, MA. NFPA 72C, Remote Station Protective Signaling Systems, 1986 edition, National Fire Protection Association, Quincy, MA. NFPA 72D, Proprietary Protective Signaling Systenns, 1986 edition, National Fire Protection Association, Quincy, MA. NFPA 72E, Automatic Fire Detectors, 1987 edition, Na- tional Fire Protection Association, Quincy, MA. NFPA 72F, Installation Maintenance and Use of Emer- gency Voice/Alarm Communication Systenns, 1985 edi- tion, National Fire Protection Associaton, Quincy, MA. NFPA 72H, Testing Procedures for Local, Auxiliarv, Re- mote Station, and Proprietary Protective Signaling Systems, 1988 edition, National Fire Protection Asso• ciation, Quincy, MA. 2007 National Fire Alarm Code Handbook PLW waterworks August 7, 2020 Mrs. Andrea Brinkley Assistant Director Baytown Area Water Authority The City of Baytown 2401 Market St. Baytown, TX 77520 Re: CPR No. #077 BAWA 6 MGD Surface Water Treatment Plant BAWA Job No. 1806021 Mrs. Brinkley, Please see attached proposal for the secondary containment areas in the Operations Building per RFP #015. This change will result in a increase in the amount of $5,905.44. Please feel free to contact me at (713) 301-8637 with any questions or concerns. Regards, P/LW Waterworks l Katy Drown Project Manager Page 1 Baytown Area Water Authority BAWA 6 NIGD Surface Water Treatment Plant BAWA Job No. 1806021 Chemical Containment Scope of Work Secondary Chemical Containment CPR No.: #077 Date: 08/07/20 PLN Job No.: P3T Non -Taxed Labor Material Subcontract Taxed Mat'I/E ui Unit Total Unit Total Unit Total Unit Total Item No. Description Qty Unit Cost Cost Cost Cost Cost Cost Cost Cost 1 Sodium Chlorite Temporary Chemical Containment 1 1 Ultratech IBC Containment Una 2 EA S - $ - S 25000 S 50000 S S $ 1.25800 S 2,51600 1 2 Forklift w.' Operator 8 HRS S 5000 S 40000 $ - $ - S S S 65000 S 65000 13 Installation of chemical contatment 16 HRS S 3900 S 60800 S S - S S S S - Direct Cost Subtotal 1,00800 50000 3,166 00 Small Tools a, 5.0% 5040 n/a n/a n/a Equipment Burden a 50.0% n/a n/a n/a n/a Tax to 8.25 % n/a n/a n/a 26120 Subtotal 2 1,05840 50000 3,42720 Overhead & Profit Ot 15.0 % 15876 7500 51408 Subtotal 3 1,217 16 57500 3,94127 Bonds & Insurance to 3.0% 3651 1725 11824 Subtotal 4 1,253 6' 59225 4,0595 Total of all columns 5,90544 Other Grand Total Cost 5,905.44 Page 2 JONES CARTER RFP NO.: 015 REQUEST FOR PROPOSAL (RFP) 1. PROJECT NAME: 6 MGD Surface Water Treatment Plant 2. AC PROJECT NO.: 09986-0002-00 3. CONTRACTOR: Pepper Lawson Waterworks 4. SUBMITTED TO: Katy Drown S. SUBJECT: Sodium Chlorite Temporary Chemical Containment 6. REFERENCE: Attached Markups 7. REF. DWG. NO.: N/A S. REF. SPEC. NO.: 9. DESCRIPTION OF WORK: The Contractor is requested to furnish a price proposal for the below described work. Please complete, sign, date, and return a proposal at your earliest convenience. Please attach a detailed cost breakdown to your proposal. 1. Contractor shall purchase and install two (2) ULTRATECH IBC Containment Unit, Uncovered, 365 gal. Spill Capacity, 8500 lb from Grainger to contain the Sodium Chlorite totes and scales in the Chlorine Dioxide Generator Chemical Containment area. See attached documentation. 2. Contractor shall install additional 3/4" flexible hose as required to make the connection to the Sodium Chlorite totes. 11. Requestor's Name & Signature: Larry Weppler Date: 8/7/20 The Contractor acknowledges that this RFP is to be used to request pricing information only, and does NOT constitute a contract modification. The Contractor is NOT AUTHORIZED/DIRECTED to perform this work UNTIL/PRIOR TO written notification that a contract modification is approved. I:wp\docslconstlforms\rfi or rfp\rfpform.doc REV 14 ry Spill Control Supplies r IBC and Tank Spill Containment l IBC Containment Unit, Uncovered, 365 gal. Spill 4 Pf1_ nt , Email IBC Containment Unit, Uncovered, 365 gal. Spill Capacity, 8500 lb. 4LNV6 Mir Model i 1157 Catalog Page p 1867 UNSPS 24101905 Web Price. H ConfirmCode to determine T Add to Cart availability. $1.258.00 / each f Add to List 33101 Save This item requires special shipping additional charges may apply Jump to: % Replacement Parts r it Shipping Weight 230.01bs. Pit '• L Country of Origin USA I Country o/Origin is sub/ect to change F.. T. -- Note Product availability is real time updated and adjusted confmuously The product wrll be reserved for you when you comp/ere your '14 How can we improve our Product Images? order Af— ❑ Compare Product Details IBC spill containment unit Features polyethylene construction for chemical resistance Will not rust or corrode Large 52" x 52' deck with removable grates re . Technical Specs Item IBC Containment Produr Type Covered/Uncovered Number of IBCs Spill Containment Load Capacity IBC Spill Containment Unit IBC Containment Unit Uncovered 1 8500 lb. Spill Capacity 365 ga4 Length 62" Width 62" Height 28" Drain Included No Standards EPA 40 CFR 264 175. SPCC Material Polyethylene Spill Containment Opening No Cover Type How can we improve our Technical Specifications' Compliance and Restrictions M—e Documentation kiItratech Chemical Compatibility Guide Ultratech IBC Spill Containment Comparison Guide Ultratech IBC Spill Pallet Plus PDS Replacement Parts Need help finding replacement parts? Please use the list below or call 1-800-GRAINGER (1-800-472-4643) 2 available replacement parts for model 1157 Part Description Mfr. Part # Item # Price ..r .,.- nUKt:, Web Price Replacement Grate, Fits... $145 50 1 each per ULTBATECH 1156 Sump, Fits Brand UltraT... Ship To 33101 v Pick Up Expected to arrive Wed. Aug 12. 40KE14 Web Price Ships from supplier Expected to arrive on or $1,240 00 / each before Tue. Aug 18 +Add to List Add to Cart Alternate Search Terms Secondary Spill Containment 6262) Containment Basins (555) IBC (Intermediate Bulk Container) Spill Control 1411 IBC ilntermethate Bulk Container) Spill Control Units [1)0) Tank Cwntauiment Units (88) Related Products l� em tt 4LNV6 ucket Shelf, Polyethylene, or Use With Ultra -IBC Spill allet® Plus, 19-1/2" ength, 16" Width LTRATECH Jeb Price 9 I 140.50 / each j i 1 Customers Also Purchased ULTRATECH Uncovered, 605 gal. Spill Capacity Item # 3FTX1 Web Price O ($868,00 / each UAdd to Cart EAGLE Spill Containment Platforms, Uncovered, 60-1/2 gal. Spill Capacity, 10,000 lb. Rem # 35UO65 Web Price 6 ($260.00 / each UAdd to Cart it ULTRATECH Bucket Shelf, Polyethylene, For Use With Ultra -IBC Spill Pallet F, Plus, 19-112" Length, 16" Width Item # 4LNV8 Web Price 6 ($140.50 / each I l I Add to Cart PiG Spill Kit/Station, Cart, Chemical, Hazmat, 14 gal. Item # 30RE80 Web Price 9 ($708.00 / each UAdd to Cart 0 ULTRATECH Spill Tray, Polyethylene, 30> gal Spill Capacity, 30" Length,48" Width,4-314" Height Item # 3FTZ7 Web Price 9 ($126.50 / each UAdd to Cart